Figures

DGX B300 port, BMC & power tables.

The tables a rack engineer needs on the day a node arrives. All from the NVIDIA DGX B300 User Guide, Introduction to NVIDIA DGX B300 Systems, last updated Jan 20, 2026.

OSFP port designation

Eight OSFP ports sit on the GPU tray; two slot ports sit on the motherboard. The default names below are what DGX OS shows; the optional column is the InfiniBand naming when a port is switched.

PortPCI busDefaultRDMAOptionalRDMA (opt.)
OSFP1 P1 lefted:00.0eno13np0 / enp237s0f0np0mlx5_22ibo13 / ibp237s0mlx5_15
OSFP1 P2 righted:00.1enp237s0f1np1mlx5_23
OSFP2 P1 left97:00.0eno10np0 / enp151s0f0np0mlx5_14ibo10 / ibp151s0mlx5_10
OSFP2 P2 right97:00.1enp151s0f1np1mlx5_15
OSFP3 P1 leftdc:00.0eno12np0 / enp220s0f0np0mlx5_20ibo12 / ibp220s0mlx5_14
OSFP3 P2 rightdc:00.1enp220s0f1np1mlx5_21
OSFP4 P1 leftb9:00.0eno11np0 / enp185s0f0np0mlx5_16ibo11 / ibp185s0mlx5_11
OSFP4 P2 rightb9:00.1enp185s0f1np1mlx5_17
OSFP5 P1 left17:00.0eno6np0 / enp23s0f0np0mlx5_0ibo6 / ibp23s0mlx5_0
OSFP5 P2 right17:00.1enp23s0f1np1mlx5_1
OSFP6 P1 left70:00.0eno9np0 / enp112s0f0np0mlx5_12ibo9 / ibp112s0mlx5_9
OSFP6 P2 right70:00.1enp112s0f1np1mlx5_13
OSFP7 P1 left39:00.0eno7np0 / enp57s0f0np0mlx5_6ibo7 / ibp57s0mlx5_5
OSFP7 P2 right39:00.1enp57s0f1np1mlx5_7
OSFP8 P1 left5f:00.0eno8np0 / enp95s0f0np0mlx5_10ibo8 / ibp95s0mlx5_8
OSFP8 P2 right5f:00.1enp95s0f1np1mlx5_11
Slot 1 port 1cc:00.0ibp204s0f0mlx5_18enp204s0f0np0mlx5_12
Slot 1 port 2cc:00.1enp204s0f1np1mlx5_19ibp204s0f1mlx5_13
Slot 2 port 153:00.0ibp83s0f0mlx5_8enp83s0f0np0mlx5_6
Slot 2 port 253:00.1enp83s0f1np1mlx5_9ibp83s0f1mlx5_7
On-board2a:00.0eno1n/an/a

Cables & adapters are not shipped with the node. Supported cables are set by the ConnectX-8 firmware; NVIDIA's adapter firmware release pages list validated cables & switches per firmware. BlueField-3 DPUs can be placed in NIC mode per NVIDIA's BlueField documentation.

Power button & LEDs

Power buttonGreen flashing 1 Hz: standby, BMC booted · green flashing 4 Hz: POST in progress · green solid: powered on
ID / UID buttonBlue LED at the front & a flashing LED at the rear for servicing; configurable from the BMC
Fault LEDAmber: system or component fault
BMC resetMotherboard button; press to reset the BMC by hand
BMC port LEDsLeft: solid green 100M, solid amber 1G · right: green flashing on activity

PSU rules

  • Twelve PSUs, N+N. Minimum six for redundancy.
  • Boots with three PSUs operational; fewer & only the BMC is available.
  • Replace a failed PSU immediately; never run depopulated.
  • AC: 3.3 kW per supply at 200 to 240 V, 16 A, 50 to 60 Hz, 15 kW system max. DC: 54 V, 300 A max, 15 kW system max.
  • PDU side: push to insert, squeeze the clips to remove. PSU side twist-lock: unlock before push or pull.